Claim this page from the supplier portal: register as a supplier (company name and contact email), open the Company tab and claim the brand. The listings are then attributed to your company page, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the supplier portal
| Fin-and-tube coil model (Elmahdy & Biggs air side, Gnielinski/Dittus-Boelter bracket water side, computed fin efficiency, contact resistance) | 36 | total capacity RMS 1.21 %, worst 2.0 %; sensible RMS 0.98 %; leaving RH within 0.5 points on average (re-read 27 Aug on the corrected saturation line, calibration 0.81) |
| Dry-coil Colburn j-factor and whole-coil UA | 38 + 1 | j +13.3 % mean against 38 measured points (inside the 3–18 % contact resistance the thesis folds into its own j); UA 0.6380 against a measured 0.6327 kW/K — 0.8 % (0.14 % at the pre-27-Aug calibration) |
| Heat-pipe recovery effectiveness | 3 sizes | within 1 point of ACT's selection |
| Moist-air saturation line (IAPWS-IF97 water line with Buck's 1981 enhancement factor) | 6 | within 0.1 % at every point — a flat 1.015 factor had put the line about 1 % high until 27 Aug |
From the validation page; every row is held by a test.
Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.