Catalog · ACT (Advanced Cooling Technologies)

ACT WAHX 12-8 wrap-around heat pipe, 1473×1100 face (sized for 4 m³/s)

Heat pipe — Heat-pipe wrap, 1473 × 1100 mm face, 8 rows at 12.0 fpi.

A ACT (Advanced Cooling Technologies) listing, from the manufacturer's published data.

Published specification

Face height1473 mm
Face length1100 mm
Rows8
Fins per inch12.0
Primary air flow4.00 m³/s
Secondary air flow4.00 m³/s

Manufacturer's product page →

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

heatPipesACT WAHX 12-4 wrap-around heat pipe, 1473×1100 face (sized for 4 m³/s)
heatPipesACT WAHX 12-6 wrap-around heat pipe, 1473×1100 face (sized for 4 m³/s)

How the model reads against this maker's data

Fin-and-tube coil model (Elmahdy & Biggs air side, Gnielinski/Dittus-Boelter bracket water side, computed fin efficiency, contact resistance)36total capacity RMS 1.21 %, worst 2.0 %; sensible RMS 0.98 %; leaving RH within 0.5 points on average (re-read 27 Aug on the corrected saturation line, calibration 0.81)
Dry-coil Colburn j-factor and whole-coil UA38 + 1j +13.3 % mean against 38 measured points (inside the 3–18 % contact resistance the thesis folds into its own j); UA 0.6380 against a measured 0.6327 kW/K — 0.8 % (0.14 % at the pre-27-Aug calibration)
Heat-pipe recovery effectiveness3 sizeswithin 1 point of ACT's selection
Moist-air saturation line (IAPWS-IF97 water line with Buck's 1981 enhancement factor)6within 0.1 % at every point — a flat 1.015 factor had put the line about 1 % high until 27 Aug

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy