The saturation line of every refrigerant the catalog's 9741 compressor maps run on — 24 fluids — as a pressure–temperature table in kPa, bar and psig every 5 K, with the latent heat, the liquid and vapour densities and, on a zeotrope, the bubble line and the glide. Each chart lists the machines on its fluid.
| Refrigerant | Type | Boiling point °C | Pressure at 0 °C, bar | Critical pressure, bar | Glide at 0 °C, K | Compressor maps |
|---|---|---|---|---|---|---|
| R404A | zeotropic blend | -45.5 | 6.00 | 37.3 | 0.5 | 1129 |
| R134a | pure fluid | -26.1 | 2.93 | 40.6 | 0 | 1063 |
| R407C | zeotropic blend | -36.6 | 4.61 | 46.3 | 6.3 | 941 |
| R448A | zeotropic blend | -39.7 | 5.11 | 40.8 | 6.1 | 841 |
| R22 | pure fluid | -40.8 | 4.98 | 49.9 | 0 | 735 |
| R449A | zeotropic blend | -39.8 | 5.11 | 38.7 | 5.7 | 657 |
| R290 | pure fluid | -42.1 | 4.74 | 42.5 | 0 | 541 |
| R410A | near-azeotropic blend | -51.4 | 7.98 | 49.0 | 0.1 | 504 |
| R407F | zeotropic blend | -39.7 | 5.22 | 47.5 | 5.6 | 479 |
| R407A | zeotropic blend | -38.6 | 4.98 | 45.1 | 5.6 | 477 |
| R454C | zeotropic blend | -37.2 | 4.42 | 43.7 | 8.3 | 348 |
| R455A | zeotropic blend | -38.6 | 4.72 | 37.4 | 12.9 | 342 |
| R600a | pure fluid | -11.7 | 1.57 | 36.3 | 0 | 325 |
| R452A | zeotropic blend | -42.9 | 5.57 | 33.7 | 4.2 | 320 |
| R513A | near-azeotropic blend | -29.3 | 3.23 | 29.5 | 0 | 307 |
| R507A | pure fluid | -46.7 | 6.24 | 37.0 | 0 | 247 |
| R454A | zeotropic blend | -41.4 | 5.30 | 40.1 | 6.8 | 214 |
| R454B | zeotropic blend | -49.5 | 7.32 | 42.7 | 1.5 | 106 |
| R1234yf | pure fluid | -29.5 | 3.16 | 33.8 | 0 | 85 |
| R32 | pure fluid | -51.7 | 8.13 | 57.8 | 0 | 44 |
| R450A | zeotropic blend | -23.0 | 2.56 | 39.0 | 0.6 | 32 |
| R422D | zeotropic blend | -38.4 | 4.83 | 35.4 | 3.8 | 2 |
| R245fa | pure fluid | 15.0 | 0.53 | 36.5 | 0 | 1 |
| R502 | near-azeotropic blend | -44.3 | 5.54 | 37.2 | 0.2 | 1 |
Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on; pressures are absolute, the boiling point is the dew temperature at 101.325 kPa, and the glide is the dew-to-bubble difference at one pressure. Superheat is measured from the dew line and subcooling from the bubble line — superheat, subcooling.
Read a compressor map at your conditions Psychrometric chart