Catalog · Refrigerants

R134a pressure–temperature chart

R134a is a pure fluid. Its normal boiling point is -26.1 °C; the critical pressure is 40.6 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 3.77 and 14.70 bar, a pressure ratio of 3.90.

Units: SI · US customary

Saturation table, -75 to 100 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-755.50.055-13.9246.715150.34
-708.00.080-13.5243.815020.49
-6511.40.114-13.0240.914880.68
-6015.90.159-12.4237.914740.93
-5521.80.218-11.5235.014601.25
-5029.50.295-10.4232.014461.65
-4539.10.391-9.0228.914322.15
-4051.20.512-7.3225.914182.77
-3566.10.661-5.1222.714033.52
-3084.40.844-2.5219.513884.43
-25106.41.0640.7216.313735.51
-20132.71.3274.6212.913586.78
-15163.91.6399.1209.513438.29
-10200.62.00614.4206.0132710.04
-5243.32.43320.6202.3131112.08
0292.82.92827.8198.6129514.43
5349.73.49736.0194.7127817.13
10414.64.14645.4190.7126120.23
15488.44.88456.1186.6124323.76
20571.75.71768.2182.3122527.78
25665.46.65481.8177.8120732.35
30770.27.70297.0173.1118737.54
35887.08.870113.9168.2116843.42
401016.610.166132.7163.0114750.09
451159.911.599153.5157.6112557.66
501317.913.179176.4151.8110266.27
551491.514.915201.6145.7107876.10
601681.816.818229.2139.1105387.38
651889.818.898259.4132.11026100.40
702116.821.168292.3124.4996115.57
752364.123.641328.2115.9964133.49
802633.226.332367.2106.4928155.08
852925.829.258409.795.5887181.85
903244.232.442455.882.5838216.76
953591.235.912506.265.4773267.14
1003972.439.724561.434.4651373.01

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.0, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R134a.

R134a compressors in the catalog

1,464 compressor maps run on R134a, each a page with its AHRI 540 / EN 12900 map across the published envelope, and each selectable in the builder. Read any of them at your own evaporating and condensing temperatures →

The largest at the air-conditioning point

Open the R134a chart in the app — the pressure–temperature line drawn, readable at any point, with a compressor's envelope over it — or open the builder and draw a circuit on R134a: the solver finds its evaporating and condensing temperatures from the coils and the compressor's map.