R410A is a near-azeotropic blend. Its normal boiling point is -51.4 °C; the critical pressure is 49.0 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 9.98 and 33.86 bar, a pressure ratio of 3.39.
| °C | kPa abs | bar abs | psig | hfg kJ/kg | ρ liquid kg/m³ | ρ vapour kg/m³ |
|---|---|---|---|---|---|---|
| -70 | 35.4 | 0.354 | -9.6 | 288.0 | 1407 | 1.56 |
| -65 | 48.0 | 0.480 | -7.7 | 284.0 | 1392 | 2.07 |
| -60 | 64.0 | 0.640 | -5.4 | 280.0 | 1376 | 2.71 |
| -55 | 83.9 | 0.839 | -2.5 | 275.8 | 1361 | 3.50 |
| -50 | 108.6 | 1.086 | 1.0 | 271.6 | 1345 | 4.45 |
| -45 | 138.6 | 1.386 | 5.4 | 267.3 | 1329 | 5.61 |
| -40 | 174.9 | 1.749 | 10.7 | 262.8 | 1313 | 6.99 |
| -35 | 218.1 | 2.181 | 16.9 | 258.3 | 1296 | 8.63 |
| -30 | 269.4 | 2.694 | 24.4 | 253.6 | 1280 | 10.55 |
| -25 | 329.4 | 3.294 | 33.1 | 248.7 | 1263 | 12.80 |
| -20 | 399.3 | 3.993 | 43.2 | 243.7 | 1245 | 15.42 |
| -15 | 480.1 | 4.801 | 54.9 | 238.4 | 1227 | 18.45 |
| -10 | 572.7 | 5.727 | 68.4 | 233.0 | 1209 | 21.94 |
| -5 | 678.3 | 6.783 | 83.7 | 227.3 | 1190 | 25.96 |
| 0 | 798.1 | 7.981 | 101.1 | 221.4 | 1170 | 30.58 |
| 5 | 933.2 | 9.332 | 120.7 | 215.2 | 1150 | 35.86 |
| 10 | 1084.8 | 10.848 | 142.6 | 208.6 | 1128 | 41.91 |
| 15 | 1254.3 | 12.543 | 167.2 | 201.7 | 1106 | 48.84 |
| 20 | 1442.9 | 14.429 | 194.6 | 194.3 | 1083 | 56.80 |
| 25 | 1652.2 | 16.522 | 224.9 | 186.5 | 1059 | 65.95 |
| 30 | 1883.4 | 18.834 | 258.5 | 178.1 | 1033 | 76.52 |
| 35 | 2138.4 | 21.384 | 295.4 | 169.0 | 1005 | 88.81 |
| 40 | 2418.6 | 24.186 | 336.1 | 159.1 | 976 | 103.24 |
| 45 | 2726.2 | 27.262 | 380.7 | 148.2 | 943 | 120.38 |
| 50 | 3063.0 | 30.630 | 429.6 | 136.0 | 907 | 141.15 |
| 55 | 3431.6 | 34.316 | 483.0 | 122.0 | 865 | 167.05 |
| 60 | 3834.9 | 38.349 | 541.5 | 105.2 | 815 | 200.97 |
| 65 | 4276.4 | 42.764 | 605.5 | 83.2 | 748 | 249.93 |
Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R410A.