Catalog · Refrigerants

R502 pressure–temperature chart

R502 is a near-azeotropic blend. Its normal boiling point is -44.3 °C. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 6.91 and 22.81 bar, a pressure ratio of 3.30. As a near-azeotropic blend it evaporates and condenses over a range of temperatures at one pressure — a glide of 0.2 K at 0.0 °C — so the dew line (where the last liquid boils off) and the bubble line (where the first vapour forms) are both tabulated. Superheat is measured up from the dew temperature and subcooling down from the bubble temperature; a map's 8.3 K of subcooling is 8.3 K under the bubble line, not the dew line, and this solver reads it so.

Units: SI · US customary

Saturation table, -75 to 70 °C

Dew °CBubble °CGlide KkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-75-75.80.818.40.184-12.0188.215851.26
-70-70.70.725.30.253-11.0185.915701.70
-65-65.70.734.20.342-9.7183.615552.25
-60-60.60.645.50.455-8.1181.315392.93
-55-55.60.659.60.596-6.1178.915233.77
-50-50.50.577.00.770-3.5176.515074.78
-45-45.50.598.10.981-0.5174.114916.00
-40-40.40.4123.51.2353.2171.614757.45
-35-35.40.4153.81.5387.6169.014589.15
-30-30.30.3189.51.89512.8166.3144111.14
-25-25.30.3231.32.31318.9163.6142413.45
-20-20.30.3279.82.79825.9160.7140716.12
-15-15.20.2335.73.35734.0157.8138919.19
-10-10.20.2399.63.99643.3154.7137022.70
-5-5.20.2472.24.72253.8151.5135126.69
0-0.20.2554.35.54365.7148.2133231.23
54.90.1646.66.46679.1144.7131236.37
109.90.1749.87.49894.1141.1129242.19
1514.90.1864.88.648110.7137.3127148.76
2019.90.1992.39.923129.2133.3124956.19
2524.90.11133.211.332149.7129.0122664.59
3029.90.11288.312.883172.2124.5120274.10
3535.00.01458.514.585196.8119.8117784.91
4040.00.01644.816.448223.9114.7115097.23
4545.00.01848.218.482253.4109.11122111.38
5050.00.02069.920.699285.5103.11092127.76
5555.00.02310.923.109320.596.51059146.97
6060.00.02572.825.728358.589.21022169.90
6565.00.02857.228.572399.780.7980198.03
7070.00.03166.231.662444.570.7931234.09

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.0, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R502.