R1234yf pressure–temperature chart

R1234yf is a pure fluid. Its normal boiling point is -29.5 °C; the critical pressure is 33.8 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 4.00 and 14.44 bar, a pressure ratio of 3.61.

Saturation table, -75 to 90 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-757.90.079-13.6203.413830.55
-7011.10.111-13.1201.113710.76
-6515.40.154-12.5198.713581.03
-6021.00.210-11.6196.313451.37
-5528.20.282-10.6193.913321.81
-5037.20.372-9.3191.413192.34
-4548.40.484-7.7188.913062.99
-4062.20.622-5.7186.412923.78
-3578.90.789-3.3183.812784.72
-3098.90.989-0.3181.112655.84
-25122.81.2283.1178.412517.16
-20150.91.5097.2175.612368.70
-15183.71.83711.9172.7122210.48
-10221.82.21817.5169.7120712.55
-5265.72.65723.8166.7119214.92
0315.93.15931.1163.5117617.63
5373.03.73039.4160.2116020.73
10437.64.37648.8156.7114424.25
15510.45.10459.3153.2112728.24
20591.85.91871.1149.4111032.77
25682.76.82784.3145.5109237.89
30783.67.83699.0141.4107343.68
35895.38.953115.2137.0105450.24
401018.510.185133.0132.4103457.67
451153.911.539152.7127.5101266.12
501302.313.023174.2122.399075.75
551464.714.647197.7116.796686.80
601641.816.418223.4110.694199.55
651834.718.347251.4104.0913114.43
702044.520.445281.896.6882132.04
752272.222.722314.988.3848153.32
802519.525.195350.778.6809179.91
852788.127.881389.766.9761215.17
903080.830.808432.150.8696268.81

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R1234yf.

R1234yf compressors in the catalog

85 compressor maps run on R1234yf, each a page with its AHRI 540 / EN 12900 map across the published envelope, and each selectable in the builder. Read any of them at your own evaporating and condensing temperatures →

The largest at the air-conditioning point

Open the builder — draw a circuit on R1234yf, and the solver finds its evaporating and condensing temperatures from the coils and the compressor's map.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · refrigerants · tools · Systems · Components · Suppliers · Privacy