R513A is a near-azeotropic blend. Its normal boiling point is -29.3 °C; the critical pressure is 29.5 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 4.12 and 15.22 bar, a pressure ratio of 3.69.
| °C | kPa abs | bar abs | psig | hfg kJ/kg | ρ liquid kg/m³ | ρ vapour kg/m³ |
|---|---|---|---|---|---|---|
| -75 | 7.2 | 0.072 | -13.6 | 219.9 | 1436 | 0.48 |
| -70 | 10.3 | 0.103 | -13.2 | 217.3 | 1423 | 0.67 |
| -65 | 14.5 | 0.145 | -12.6 | 214.7 | 1410 | 0.92 |
| -60 | 20.0 | 0.200 | -11.8 | 212.1 | 1396 | 1.24 |
| -55 | 27.0 | 0.270 | -10.8 | 209.4 | 1383 | 1.64 |
| -50 | 36.0 | 0.360 | -9.5 | 206.7 | 1369 | 2.15 |
| -45 | 47.2 | 0.472 | -7.9 | 204.0 | 1355 | 2.77 |
| -40 | 61.0 | 0.610 | -5.8 | 201.2 | 1341 | 3.52 |
| -35 | 77.9 | 0.779 | -3.4 | 198.3 | 1327 | 4.43 |
| -30 | 98.3 | 0.983 | -0.4 | 195.4 | 1313 | 5.51 |
| -25 | 122.7 | 1.227 | 3.1 | 192.5 | 1298 | 6.80 |
| -20 | 151.6 | 1.516 | 7.3 | 189.4 | 1284 | 8.30 |
| -15 | 185.5 | 1.855 | 12.2 | 186.3 | 1268 | 10.05 |
| -10 | 225.1 | 2.251 | 17.9 | 183.0 | 1253 | 12.08 |
| -5 | 270.7 | 2.707 | 24.6 | 179.7 | 1237 | 14.43 |
| 0 | 323.2 | 3.232 | 32.2 | 176.2 | 1221 | 17.11 |
| 5 | 383.0 | 3.830 | 40.9 | 172.6 | 1205 | 20.19 |
| 10 | 450.9 | 4.509 | 50.7 | 168.9 | 1188 | 23.70 |
| 15 | 527.6 | 5.276 | 61.8 | 165.0 | 1171 | 27.68 |
| 20 | 613.6 | 6.136 | 74.3 | 161.0 | 1153 | 32.20 |
| 25 | 709.8 | 7.098 | 88.3 | 156.8 | 1134 | 37.33 |
| 30 | 816.9 | 8.169 | 103.8 | 152.3 | 1115 | 43.14 |
| 35 | 935.6 | 9.356 | 121.0 | 147.7 | 1095 | 49.72 |
| 40 | 1066.7 | 10.667 | 140.0 | 142.7 | 1074 | 57.18 |
| 45 | 1211.1 | 12.111 | 161.0 | 137.5 | 1052 | 65.66 |
| 50 | 1369.6 | 13.696 | 184.0 | 132.0 | 1029 | 75.33 |
| 55 | 1543.2 | 15.432 | 209.1 | 126.0 | 1005 | 86.41 |
| 60 | 1732.9 | 17.329 | 236.6 | 119.5 | 979 | 99.20 |
| 65 | 1939.6 | 19.396 | 266.6 | 112.5 | 950 | 114.10 |
| 70 | 2164.6 | 21.646 | 299.2 | 104.7 | 919 | 131.69 |
| 75 | 2409.1 | 24.091 | 334.7 | 96.0 | 884 | 152.88 |
Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R513A.