R513A pressure–temperature chart

R513A is a near-azeotropic blend. Its normal boiling point is -29.3 °C; the critical pressure is 29.5 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 4.12 and 15.22 bar, a pressure ratio of 3.69.

Saturation table, -75 to 75 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-757.20.072-13.6219.914360.48
-7010.30.103-13.2217.314230.67
-6514.50.145-12.6214.714100.92
-6020.00.200-11.8212.113961.24
-5527.00.270-10.8209.413831.64
-5036.00.360-9.5206.713692.15
-4547.20.472-7.9204.013552.77
-4061.00.610-5.8201.213413.52
-3577.90.779-3.4198.313274.43
-3098.30.983-0.4195.413135.51
-25122.71.2273.1192.512986.80
-20151.61.5167.3189.412848.30
-15185.51.85512.2186.3126810.05
-10225.12.25117.9183.0125312.08
-5270.72.70724.6179.7123714.43
0323.23.23232.2176.2122117.11
5383.03.83040.9172.6120520.19
10450.94.50950.7168.9118823.70
15527.65.27661.8165.0117127.68
20613.66.13674.3161.0115332.20
25709.87.09888.3156.8113437.33
30816.98.169103.8152.3111543.14
35935.69.356121.0147.7109549.72
401066.710.667140.0142.7107457.18
451211.112.111161.0137.5105265.66
501369.613.696184.0132.0102975.33
551543.215.432209.1126.0100586.41
601732.917.329236.6119.597999.20
651939.619.396266.6112.5950114.10
702164.621.646299.2104.7919131.69
752409.124.091334.796.0884152.88

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R513A.

R513A compressors in the catalog

307 compressor maps run on R513A, each a page with its AHRI 540 / EN 12900 map across the published envelope, and each selectable in the builder. Read any of them at your own evaporating and condensing temperatures →

The largest at the air-conditioning point

Open the builder — draw a circuit on R513A, and the solver finds its evaporating and condensing temperatures from the coils and the compressor's map.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · refrigerants · tools · Systems · Components · Suppliers · Privacy