Compressor — R513A compressor — 134.0 kW cooling, 47.45 kW input, COP 2.82 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZHT300KCE-TED (R513A scroll, 60 Hz, HR) |
| Refrigerant | R513A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 133.97 kW |
| Input power @ 7.2/54.4 °C | 47.45 kW |
| COP @ 7.2/54.4 °C | 2.82 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 7-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 20 | 100.58 | 22.68 | 4.43 |
| -10 / 50 | 69.51 | 41.04 | 1.69 |
| 0 / 20 | 149.36 | 25.37 | 5.89 |
| 0 / 50 | 107.14 | 42.65 | 2.51 |
| 20 / 50 | 228.46 | 46.53 | 4.91 |
| 20 / 80 | 133.25 | 77.57 | 1.72 |
| 40 / 80 | 277.10 | 80.77 | 3.43 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.