Catalog · Refrigerants

R600a pressure–temperature chart

R600a is a pure fluid. Its normal boiling point is -11.7 °C; the critical pressure is 36.3 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 2.01 and 7.62 bar, a pressure ratio of 3.79.

Saturation table, -75 to 130 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-753.30.033-14.2415.86600.12
-704.80.048-14.0412.06550.17
-656.70.067-13.7408.36500.23
-609.30.093-13.4404.46450.31
-5512.60.126-12.9400.66400.41
-5016.80.168-12.3396.76340.53
-4522.10.221-11.5392.86290.69
-4028.70.287-10.5388.86240.88
-3536.80.368-9.4384.86191.10
-3046.60.466-7.9380.76141.37
-2558.40.584-6.2376.66081.69
-2072.50.725-4.2372.36032.07
-1589.10.891-1.8368.05972.51
-10108.51.0851.0363.55923.01
-5131.01.3104.3359.05863.59
0157.01.5708.1354.35814.26
5186.71.86712.4349.65755.01
10220.62.20617.3344.65695.87
15259.02.59022.9339.65636.83
20302.23.02229.1334.35577.91
25350.73.50736.2328.95519.13
30404.74.04744.0323.354410.48
35464.84.64852.7317.553811.99
40531.25.31262.3311.553113.67
45604.46.04473.0305.352415.53
50684.96.84984.6298.851717.60
55773.07.73097.4292.051019.89
60869.28.692111.4284.950322.43
65973.99.739126.5277.449525.24
701087.510.875143.0269.648728.37
751210.712.107160.9261.347931.85
801343.813.438180.2252.647035.72
851487.414.874201.0243.346140.06
901642.016.420223.5233.345144.93
951808.118.081247.6222.644150.43
1001986.519.865273.4211.043056.70
1052177.821.778301.2198.441863.91
1102382.623.826330.9184.440472.33
1152601.926.019362.7168.538982.37
1202836.628.366396.7150.237294.74
1253088.030.880433.2127.8351110.87
1303357.833.578472.397.2321134.72

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R600a.

R600a compressors in the catalog

325 compressor maps run on R600a, each a page with its AHRI 540 / EN 12900 map across the published envelope, and each selectable in the builder. Read any of them at your own evaporating and condensing temperatures →

The largest at the air-conditioning point

Open the builder — draw a circuit on R600a, and the solver finds its evaporating and condensing temperatures from the coils and the compressor's map.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · refrigerants · tools · Systems · Components · Suppliers · Privacy