R600a is a pure fluid. Its normal boiling point is -11.7 °C; the critical pressure is 36.3 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 2.01 and 7.62 bar, a pressure ratio of 3.79.
| °C | kPa abs | bar abs | psig | hfg kJ/kg | ρ liquid kg/m³ | ρ vapour kg/m³ |
|---|---|---|---|---|---|---|
| -75 | 3.3 | 0.033 | -14.2 | 415.8 | 660 | 0.12 |
| -70 | 4.8 | 0.048 | -14.0 | 412.0 | 655 | 0.17 |
| -65 | 6.7 | 0.067 | -13.7 | 408.3 | 650 | 0.23 |
| -60 | 9.3 | 0.093 | -13.4 | 404.4 | 645 | 0.31 |
| -55 | 12.6 | 0.126 | -12.9 | 400.6 | 640 | 0.41 |
| -50 | 16.8 | 0.168 | -12.3 | 396.7 | 634 | 0.53 |
| -45 | 22.1 | 0.221 | -11.5 | 392.8 | 629 | 0.69 |
| -40 | 28.7 | 0.287 | -10.5 | 388.8 | 624 | 0.88 |
| -35 | 36.8 | 0.368 | -9.4 | 384.8 | 619 | 1.10 |
| -30 | 46.6 | 0.466 | -7.9 | 380.7 | 614 | 1.37 |
| -25 | 58.4 | 0.584 | -6.2 | 376.6 | 608 | 1.69 |
| -20 | 72.5 | 0.725 | -4.2 | 372.3 | 603 | 2.07 |
| -15 | 89.1 | 0.891 | -1.8 | 368.0 | 597 | 2.51 |
| -10 | 108.5 | 1.085 | 1.0 | 363.5 | 592 | 3.01 |
| -5 | 131.0 | 1.310 | 4.3 | 359.0 | 586 | 3.59 |
| 0 | 157.0 | 1.570 | 8.1 | 354.3 | 581 | 4.26 |
| 5 | 186.7 | 1.867 | 12.4 | 349.6 | 575 | 5.01 |
| 10 | 220.6 | 2.206 | 17.3 | 344.6 | 569 | 5.87 |
| 15 | 259.0 | 2.590 | 22.9 | 339.6 | 563 | 6.83 |
| 20 | 302.2 | 3.022 | 29.1 | 334.3 | 557 | 7.91 |
| 25 | 350.7 | 3.507 | 36.2 | 328.9 | 551 | 9.13 |
| 30 | 404.7 | 4.047 | 44.0 | 323.3 | 544 | 10.48 |
| 35 | 464.8 | 4.648 | 52.7 | 317.5 | 538 | 11.99 |
| 40 | 531.2 | 5.312 | 62.3 | 311.5 | 531 | 13.67 |
| 45 | 604.4 | 6.044 | 73.0 | 305.3 | 524 | 15.53 |
| 50 | 684.9 | 6.849 | 84.6 | 298.8 | 517 | 17.60 |
| 55 | 773.0 | 7.730 | 97.4 | 292.0 | 510 | 19.89 |
| 60 | 869.2 | 8.692 | 111.4 | 284.9 | 503 | 22.43 |
| 65 | 973.9 | 9.739 | 126.5 | 277.4 | 495 | 25.24 |
| 70 | 1087.5 | 10.875 | 143.0 | 269.6 | 487 | 28.37 |
| 75 | 1210.7 | 12.107 | 160.9 | 261.3 | 479 | 31.85 |
| 80 | 1343.8 | 13.438 | 180.2 | 252.6 | 470 | 35.72 |
| 85 | 1487.4 | 14.874 | 201.0 | 243.3 | 461 | 40.06 |
| 90 | 1642.0 | 16.420 | 223.5 | 233.3 | 451 | 44.93 |
| 95 | 1808.1 | 18.081 | 247.6 | 222.6 | 441 | 50.43 |
| 100 | 1986.5 | 19.865 | 273.4 | 211.0 | 430 | 56.70 |
| 105 | 2177.8 | 21.778 | 301.2 | 198.4 | 418 | 63.91 |
| 110 | 2382.6 | 23.826 | 330.9 | 184.4 | 404 | 72.33 |
| 115 | 2601.9 | 26.019 | 362.7 | 168.5 | 389 | 82.37 |
| 120 | 2836.6 | 28.366 | 396.7 | 150.2 | 372 | 94.74 |
| 125 | 3088.0 | 30.880 | 433.2 | 127.8 | 351 | 110.87 |
| 130 | 3357.8 | 33.578 | 472.3 | 97.2 | 321 | 134.72 |
Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R600a.