R1234ze(e) pressure–temperature chart

R1234ze(e) is a pure fluid. Its normal boiling point is -19.0 °C; the critical pressure is 36.3 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 2.80 and 11.14 bar, a pressure ratio of 3.98.

Units: SI · US customary

Saturation table, -75 to 105 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-753.80.038-14.2225.814380.26
-705.50.055-13.9223.214260.37
-657.90.079-13.5220.514130.53
-6011.20.112-13.1217.914010.72
-5515.40.154-12.5215.213880.98
-5020.90.209-11.7212.613751.30
-4527.90.279-10.6210.013621.71
-4036.70.367-9.4207.313502.21
-3547.70.477-7.8204.613362.81
-3061.10.611-5.8201.813233.55
-2577.40.774-3.5199.013104.43
-2096.90.969-0.6196.212965.47
-15120.11.2012.7193.312836.70
-10147.41.4746.7190.312698.13
-5179.41.79411.3187.312559.79
0216.62.16616.7184.2124011.71
5259.32.59322.9181.0122513.92
10308.43.08430.0177.6121016.45
15364.23.64238.1174.2119519.33
20427.34.27347.3170.6117922.61
25498.54.98557.6166.9116326.32
30578.35.78369.2163.1114630.52
35667.46.67482.1159.0112935.27
40766.57.66596.5154.8111240.64
45876.18.761112.4150.4109346.69
50997.29.972129.9145.7107453.54
551130.411.304149.3140.7105461.29
601276.612.766170.5135.5103370.08
651436.514.365193.6129.9101080.09
701611.016.110219.0123.898691.56
751801.118.011246.5117.3961104.80
802007.720.077276.5110.2933120.23
852232.122.321309.0102.3902138.48
902475.524.755344.393.4867160.57
952739.527.395382.683.0827188.22
1003026.030.260424.270.4777225.01
1053337.833.378469.452.9708281.02

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.0, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R1234ze(e).