Catalog · Refrigerants

R32 pressure–temperature chart

R32 is a pure fluid. Its normal boiling point is -51.7 °C; the critical pressure is 57.8 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 10.18 and 34.73 bar, a pressure ratio of 3.41.

Saturation table, -75 to 75 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-7526.20.262-10.9405.912750.84
-7036.10.361-9.5400.912621.14
-6548.80.488-7.6395.912491.51
-6065.00.650-5.3390.712361.97
-5585.20.852-2.3385.512222.54
-50110.11.1011.3380.112083.23
-45140.61.4065.7374.511944.07
-40177.41.77411.0368.811805.07
-35221.42.21417.4362.911666.25
-30273.42.73425.0356.811517.64
-25334.63.34633.8350.511369.27
-20405.84.05844.2344.0112111.16
-15488.14.88156.1337.3110513.35
-10582.65.82669.8330.3108915.87
-5690.66.90685.5322.9107218.77
0813.18.131103.2315.3105522.09
5951.49.514123.3307.3103825.89
101106.911.069145.8298.9102030.23
151280.812.808171.1290.1100135.19
201474.614.746199.2280.898140.86
251689.616.896230.4270.996147.34
301927.519.275264.9260.494054.78
352189.821.898302.9249.291763.34
402478.324.783344.8237.189373.27
452794.827.948390.7224.086784.86
503141.231.412440.9209.683998.55
553519.935.199495.8193.6808114.99
603933.239.332555.8175.5773135.21
654384.343.843621.2154.3732161.09
704876.848.768692.6127.8681196.69
755416.854.168770.989.3606255.59

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R32.

R32 compressors in the catalog

44 compressor maps run on R32, each a page with its AHRI 540 / EN 12900 map across the published envelope, and each selectable in the builder. Read any of them at your own evaporating and condensing temperatures →

The largest at the air-conditioning point

Open the builder — draw a circuit on R32, and the solver finds its evaporating and condensing temperatures from the coils and the compressor's map.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · refrigerants · tools · Systems · Components · Suppliers · Privacy