Catalog · Refrigerants

R245fa pressure–temperature chart

R245fa is a pure fluid. Its normal boiling point is 15.0 °C; the critical pressure is 36.5 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 0.73 and 3.93 bar, a pressure ratio of 5.37.

Saturation table, -75 to 150 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-750.30.003-14.6241.015820.03
-700.50.005-14.6238.615710.04
-650.90.009-14.6236.215600.07
-601.30.013-14.5233.815480.10
-552.00.020-14.4231.415370.15
-502.90.029-14.3229.015250.21
-454.10.041-14.1226.615130.29
-405.80.058-13.8224.315010.41
-358.10.081-13.5221.914900.55
-3011.00.110-13.1219.514780.74
-2514.80.148-12.5217.114660.97
-2019.60.196-11.9214.714541.27
-1525.60.256-11.0212.214411.63
-1033.10.331-9.9209.814292.07
-542.20.422-8.6207.314172.60
053.30.533-7.0204.714043.23
566.60.666-5.0202.113913.98
1082.40.824-2.7199.513784.87
15101.11.011-0.0196.813655.91
20123.11.2313.2194.013527.11
25148.61.4866.9191.213388.50
30178.11.78111.1188.3132510.10
35212.02.12016.0185.4131111.93
40250.62.50621.7182.3129714.01
45294.62.94628.0179.2128216.37
50344.23.44235.2175.9126719.05
55400.04.00043.3172.6125222.06
60462.54.62552.4169.1123725.45
65532.15.32162.5165.5122129.25
70609.36.09373.7161.8120533.52
75694.86.94886.1157.9118838.29
80789.07.89099.7153.9117043.65
85892.58.925114.8149.6115249.64
901005.910.059131.2145.2113456.36
951129.811.298149.2140.5111463.90
1001264.912.649168.8135.6109472.39
1051411.714.117190.1130.3107281.98
1101571.115.711213.2124.8104992.86
1151743.717.437238.2118.81025105.29
1201930.419.304265.3112.2999119.61
1252132.021.320294.5105.1970136.31
1302349.523.495326.197.3938156.10
1352584.125.841360.188.4903180.09
1402837.028.370396.878.0861210.22
1453109.931.099436.465.4810250.41
1503405.034.050479.248.1738311.98

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R245fa.

R245fa compressors in the catalog

1 compressor maps run on R245fa, each a page with its AHRI 540 / EN 12900 map across the published envelope, and each selectable in the builder. Read any of them at your own evaporating and condensing temperatures →

Open the builder — draw a circuit on R245fa, and the solver finds its evaporating and condensing temperatures from the coils and the compressor's map.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · refrigerants · tools · Systems · Components · Suppliers · Privacy