Catalog · Refrigerants

R507A pressure–temperature chart

R507A is a pure fluid. Its normal boiling point is -46.7 °C; the critical pressure is 37.0 bar. At the AHRI 540 air-conditioning rating point — 7.2 °C evaporating, 54.4 °C condensing — the saturation pressures are 7.78 and 26.05 bar, a pressure ratio of 3.35.

Saturation table, -70 to 65 °C

°CkPa absbar abspsighfg kJ/kgρ liquid kg/m³ρ vapour kg/m³
-7028.40.284-10.6211.213881.70
-6538.40.384-9.1208.213732.25
-6051.10.511-7.3205.213582.94
-5566.90.669-5.0202.113423.78
-5086.40.864-2.2198.913274.81
-45110.11.1011.3195.713116.04
-40138.71.3875.4192.512967.51
-35172.71.72710.3189.112809.24
-30212.82.12816.2185.6126311.28
-25259.82.59823.0182.1124613.65
-20314.43.14430.9178.4122916.41
-15377.33.77340.0174.6121219.59
-10449.34.49350.5170.6119423.24
-5531.25.31262.4166.4117527.44
0624.06.24075.8162.1115632.24
5728.47.28490.9157.5113637.74
10845.48.454107.9152.7111644.02
15975.99.759126.8147.6109451.20
201120.911.209147.9142.2107259.42
251281.512.815171.2136.5104868.87
301458.714.587196.9130.3102379.77
351653.816.538225.2123.699592.43
401867.918.679256.2116.3966107.28
452102.521.025290.2108.2934124.94
502359.223.592327.599.1898146.37
552639.926.399368.288.6856173.20
602947.029.470412.775.9806208.65
653283.632.836461.559.1739261.10

Pressures are absolute in kPa and bar, gauge in psig (at 101.325 kPa atmospheric); hfg is the latent heat of vaporisation at the dew pressure; densities are saturated liquid and saturated vapour. Computed with CoolProp 8.0.1dev, the open-source property library the solver runs on, sampled every 0.5 K and printed every 5 K — the same tables the builder reads when it solves a circuit on R507A.

R507A compressors in the catalog

247 compressor maps run on R507A, each a page with its AHRI 540 / EN 12900 map across the published envelope, and each selectable in the builder. Read any of them at your own evaporating and condensing temperatures →

The largest at the air-conditioning point

Open the builder — draw a circuit on R507A, and the solver finds its evaporating and condensing temperatures from the coils and the compressor's map.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · refrigerants · tools · Systems · Components · Suppliers · Privacy