Companies

Samsung Unclaimed

1 system(s) modelled in HVAC Builder on Samsung's published performance data and validated against it. This page is listed by HVAC Builder from published data; Samsung has not claimed it.

Are you Samsung?

Claim this page from the supplier portal: register as a supplier (company name and contact email), open the Company tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the supplier portal

Systems modelled on Samsung's published data

Built in this model on the maker's published performance grid and validated against it — not verified by Samsung. Each page names its source and says so.

Samsung DVM S AM200FXVAGH/EU (20 HP, 56 kW) — modelledSamsung VRF Technical Data Book, DVM S outdoor units for Europe (R410A, 50 Hz), ver. 1.3 — AM200FXVAGH/EU capacity table (H/P standard), 100 % combination at 19 °C indoor wet bulb (docs/samsung-vrf-source.json)

How the model reads against Samsung's data

Heat-pump frost/defrost derate43, from five makersRMS 0.023, where the makers stand 0.029 from each other at the forty temperatures they share — the one generic curve is closer to each of them than they are to one another, and none is served much worse than any other (0.019–0.028 apiece). The EnergyPlus model this replaced had the shape inverted (deepest just below its 5 °C cutoff, then a 29-point step across it) and read up to 0.15 low
Three-pipe heat recovery: SCHE, and what the outdoor coil seesthree configurations (cooling-led, heating-led, balanced) in hvac-core; the Meguro office's 635 mixed-mode hours a yearwith both sides pinned by their coils, the outdoor coil rejects (or absorbs) exactly the larger side less the recovered duty, both sides export once each, and SCHE = COP_c + COP_h by identity on a map where qc = qe + hrf·P — not COP_c + COP_h − 1, which the first draft asserted from memory and the probe corrected. On the office's Tokyo year the three-pipe unit serves both directions on 567 hours and takes the north room's unmet heating from 25 hours to 1, at electricity flat to 0.1 %: the recovered loads are trickles at the machine's floor, so what recovery buys here is the hour, not the kilowatt-hour
VRF (multi-split): capacity against the connected-capacity ratioeight makersthey agree on a two-regime law — exactly linear below 100 % connection, saturating above it by +2 to +8 % at 130 %, with Samsung allowing no credit above 130 % — and the model reproduces both without a correction term: below full connection each indoor coil caps its own take, above it the outdoor unit's map is the ceiling (+0 %, the conservative end of the band). The standards themselves rate only at unity connection (±5 %)
Samsung DVM S AM200FXVAGH/EU (20 HP), modelled — the whole machine against Samsung's published grid8modulated to Samsung's capacity, the machine draws −1 to +4 % of Samsung's power input, the compressor at 0.67–0.81 of full output; the same graph reads +1 to +4 % against Midea's 20 HP grid

From the validation page; every row is held by a test.

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy