Catalog · Carnes

Carnes VDBA 07 belt-drive forward-curved duct blower (7.75 in. wheel, 2292 rpm, 3/4 HP)

Fan — Fan rated 0.38 m³/s at 0.65 kW.

A Carnes listing, from the manufacturer's published data.

Units: SI · US customary

Published specification

Design air flow0.38 m³/s
Input power0.65 kW
Static efficiency, on input power36%
External static623 Pa
Pressure at the design flow621 Pa
Fan curve25 points
Input-power curve25 points

Manufacturer's product page

Open this part in the app — as a component of its own, carrying the catalog's figures; or open the builder and pick it from the catalog picker. The solver runs it with the catalog's own data, at your design point or across a year of weather.

Same family

FanCarnes VDBA 10 / VGBA 10 belt-drive forward-curved duct blower (11.44 in. wheel, 1583 rpm, 1-1/2 HP)
FanCarnes VDBA 18 / VGBA 18 belt-drive forward-curved duct blower (18.19 in. wheel, 857 rpm, 5 HP)
FanCarnes VDBA 27 twin belt-drive forward-curved duct blower (two 7.75 in. wheels, 2292 rpm, 1-1/2 HP)
FanCarnes VDBA 29 / VGBA 29 twin belt-drive forward-curved duct blower (two 10.13 in. wheels, 1362 rpm, 1-1/2 HP)
FanCarnes VDBA 30 / VGBA 30 twin belt-drive forward-curved duct blower (two 11.44 in. wheels, 1400 rpm, 1-1/2 HP)

How the model reads against this maker's data

Fan power through the fan laws, one curve per fan from a US multi-rating table1 632 cells over 14 fans; 230 withheld by nameevery held cell's BHP within 2 % plus the half-hundredth it is printed to (the worst at 0.985 of that band; 20 cells from 0.5 BHP read past a bare 2 %, to 2.7 %) and its speed within 1.12 %, read back by the solver's own fan-law solve; RMS 0.69 % on power over the 1 280 cells from 0.5 BHP up. The twin tables are derived from the singles, so 893 cells are printed twice: the 764 held on both sides agree (the same rpm, twice the BHP), and of the 30 pairs that do not, the print the fan laws read off is withheld — the single 18's whole 1/2 in. BHP column among them. 178 cells sit left of the forward-curved wheel's pressure peak, in the dip the falling curve does not reach, and 22 read off the fan laws; both are withheld by name. Each rating lies on its curve (the curve's static at the design flow within 0.79 % of the design static), the curve's power within the motor up to the design flow; past it the forward-curved wheel's power passes the motor on 13 of the 14, and the record says where

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.