Compressor — R407F compressor — 27.7 kW cooling, 10.07 kW input, COP 2.75 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 2DA3F23KE-TFC (R407F Discus recip, 60 Hz, LD) |
| Refrigerant | R407F |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 47.2 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 27.72 kW |
| Input power @ 7.2/54.4 °C | 10.07 kW |
| COP @ 7.2/54.4 °C | 2.75 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 10 | 6.24 | 2.14 | 2.91 |
| -40 / 30 | 3.50 | 2.56 | 1.36 |
| -30 / 10 | 10.37 | 3.15 | 3.29 |
| -30 / 30 | 7.18 | 3.62 | 1.98 |
| -30 / 60 | 3.34 | 4.00 | 0.84 |
| -20 / 10 | 15.43 | 3.52 | 4.39 |
| -20 / 30 | 12.07 | 4.45 | 2.71 |
| -20 / 60 | 6.54 | 5.52 | 1.19 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 2DA3F23KE-TFC (R407A Discus recip, 60 Hz, LD) | R407A |
| compressors | Copeland 2DA3F23KE-TFD (R407C Discus recip, 60 Hz, LD) | R407C |
| compressors | Copeland 2DA3F23KE-TFC (R448A Discus recip, 60 Hz, LD) | R448A |
| compressors | Copeland 2DA3F23KE-TFD (R513A Discus recip, 60 Hz, MD) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.