Compressor — R448A compressor with a 10-coefficient AHRI 540 map.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 2DL3F20KE-TFC (R448A Discus recip, 60 Hz, LD) |
| Refrigerant | R448A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 47.2 / 0.0 K |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 10 | 5.55 | 1.90 | 2.92 |
| -40 / 30 | 3.34 | 2.33 | 1.43 |
| -30 / 10 | 8.78 | 2.70 | 3.25 |
| -30 / 30 | 6.36 | 3.20 | 1.99 |
| -30 / 60 | 3.11 | 3.42 | 0.91 |
| -20 / 10 | 13.30 | 3.12 | 4.27 |
| -20 / 30 | 10.70 | 3.90 | 2.75 |
| -20 / 60 | 6.05 | 4.85 | 1.25 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 2DL3F20KE-TFC (R407A Discus recip, 60 Hz, LD) | R407A |
| compressors | Copeland 2DL3F20KE-TFD (R407C Discus recip, 60 Hz, LD) | R407C |
| compressors | Copeland 2DL3F20KE-TFC (R407F Discus recip, 60 Hz, LD) | R407F |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.