Catalog · Copeland

Copeland 3DF3F40KE-TFD (R407C Discus recip, 50 Hz, LT)

Compressor — R407C compressor — 37.7 kW cooling, 15.66 kW input, COP 2.41 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 3DF3F40KE-TFD (R407C Discus recip, 50 Hz, LT)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C37.67 kW
Input power @ 7.2/54.4 °C15.66 kW
COP @ 7.2/54.4 °C2.41

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 305.814.261.36
-40 / 404.534.351.04
-40 / 502.854.430.64
-30 / 3011.816.161.92
-30 / 409.936.381.56
-30 / 507.696.421.20
-20 / 3019.737.772.54
-20 / 4017.438.562.04
-20 / 5014.859.021.65

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 3DF3F40KE-TFD (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 3DF3F40KE-TFD (R407C Discus recip, 60 Hz, LT)R407C
compressorsCopeland 3DF3F40KE-TFD (R407F Discus recip, 60 Hz, LD)R407F
compressorsCopeland 3DF3F40KE-TFD (R448A Discus recip, 60 Hz, LD)R448A
compressorsCopeland 3DF3F40KE-TFD (R513A Discus recip, 60 Hz, MD)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy