Copeland 3DS3R17ME-TFD (R407C Discus recip, 60 Hz, AC)

Compressor — R407C compressor — 48.9 kW cooling, 16.88 kW input, COP 2.90 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 3DS3R17ME-TFD (R407C Discus recip, 60 Hz, AC)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C48.95 kW
Input power @ 7.2/54.4 °C16.88 kW
COP @ 7.2/54.4 °C2.90

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3036.289.833.69
-10 / 4032.4911.312.87
-10 / 6023.1513.241.75
0 / 3056.4410.585.34
0 / 4049.7712.693.92
0 / 6038.3216.572.31
10 / 3083.9310.298.16
10 / 4072.4013.015.57
10 / 6054.8518.762.92

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 3DS3R17ME-TFD (R407A Discus recip, 50 Hz, MD)R407A
compressorsCopeland 3DS3R17ME-TFD (R407A Discus recip, 60 Hz, AC)R407A
compressorsCopeland 3DS3R17ME-TFD (R407F Discus recip, 50 Hz, MD)R407F
compressorsCopeland 3DS3R17ME-TFD (R407F Discus recip, 60 Hz, MD)R407F
compressorsCopeland 3DS3R17ME-TFD (R448A Discus recip, 60 Hz, MD)R448A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy