Compressor — R407C compressor — 48.9 kW cooling, 16.88 kW input, COP 2.90 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 3DS3R17ML-TFD (R407C Discus recip, 60 Hz, AC) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 48.95 kW |
| Input power @ 7.2/54.4 °C | 16.88 kW |
| COP @ 7.2/54.4 °C | 2.90 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 36.28 | 9.83 | 3.69 |
| -10 / 40 | 32.49 | 11.31 | 2.87 |
| -10 / 60 | 23.15 | 13.24 | 1.75 |
| 0 / 30 | 56.44 | 10.58 | 5.34 |
| 0 / 40 | 49.77 | 12.69 | 3.92 |
| 0 / 60 | 38.32 | 16.57 | 2.31 |
| 10 / 30 | 83.93 | 10.29 | 8.16 |
| 10 / 40 | 72.40 | 13.01 | 5.57 |
| 10 / 60 | 54.85 | 18.76 | 2.92 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 3DS3R17ML-TFD (R407A Discus recip, 50 Hz, MD) | R407A |
| compressors | Copeland 3DS3R17ML-TFD (R407A Discus recip, 60 Hz, AC) | R407A |
| compressors | Copeland 3DS3R17ML-TFD (R407F Discus recip, 50 Hz, MD) | R407F |
| compressors | Copeland 3DS3R17ML-TFD (R407F Discus recip, 60 Hz, MD) | R407F |
| compressors | Copeland 3DS3R17ML-TFD (R448A Discus recip, 60 Hz, MD) | R448A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.