Catalog · Copeland

Copeland 3DSDS12ML-TFD (R449A Discus recip, 60 Hz, MD)

Compressor — R449A compressor — 52.4 kW cooling, 17.42 kW input, COP 3.01 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 3DSDS12ML-TFD (R449A Discus recip, 60 Hz, MD)
RefrigerantR449A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.5 / 0.0 K
Cooling capacity @ 7.2/54.4 °C52.43 kW
Input power @ 7.2/54.4 °C17.42 kW
COP @ 7.2/54.4 °C3.01

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1027.836.584.23
-20 / 3024.218.932.71
-10 / 1044.456.776.56
-10 / 3038.0310.293.69
-10 / 5029.1213.192.21

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 3DSDS12ML-TFD (R407A Discus recip, 60 Hz, MD)R407A
compressorsCopeland 3DSDS12ML-TFC (R407C Discus recip, 60 Hz, MD)R407C
compressorsCopeland 3DSDS12ML-TFD (R407F Discus recip, 60 Hz, MD)R407F
compressorsCopeland 3DSDS12ML-TFD (R448A Discus recip, 60 Hz, MD)R448A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy