Catalog · Copeland

Copeland 3YF4S87KL-TFD (R454A Discus recip, 50 Hz, MD)

Compressor — R454A compressor — 39.8 kW cooling, 13.81 kW input, COP 2.88 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 3YF4S87KL-TFD (R454A Discus recip, 50 Hz, MD)
RefrigerantR454A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.5 / 0.0 K
Cooling capacity @ 7.2/54.4 °C39.78 kW
Input power @ 7.2/54.4 °C13.81 kW
COP @ 7.2/54.4 °C2.88

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1023.265.254.43
-20 / 3018.717.132.62
-10 / 1035.395.086.97
-10 / 3029.188.233.55
-10 / 5021.8610.462.09

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 3YF4S87KL-TFD (R454A Discus recip, 60 Hz, MD)R454A
compressorsCopeland 3YF4S87KL-TFD (R454C Discus recip, 50 Hz, MD)R454C
compressorsCopeland 3YF4S87KL-TFD (R454C Discus recip, 60 Hz, MD)R454C
compressorsCopeland 3YF4S87KL-TFD (R455A Discus recip, 50 Hz, MD)R455A
compressorsCopeland 3YF4S87KL-TFD (R455A Discus recip, 60 Hz, MD)R455A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy