Compressor — R407F compressor — 61.8 kW cooling, 18.66 kW input, COP 3.31 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 4DCNR20ML-TSK (R407F Discus recip, 50 Hz, AC) |
| Refrigerant | R407F |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 61.79 kW |
| Input power @ 7.2/54.4 °C | 18.66 kW |
| COP @ 7.2/54.4 °C | 3.31 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 41.73 | 11.01 | 3.79 |
| -10 / 40 | 36.35 | 12.50 | 2.91 |
| -10 / 60 | 25.42 | 14.84 | 1.71 |
| 0 / 30 | 64.16 | 11.96 | 5.36 |
| 0 / 40 | 56.38 | 14.23 | 3.96 |
| 0 / 60 | 41.24 | 18.07 | 2.28 |
| 10 / 30 | 94.74 | 11.72 | 8.08 |
| 10 / 40 | 84.00 | 14.93 | 5.63 |
| 10 / 60 | 63.58 | 20.60 | 3.09 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 4DCNR20ML-TSK (R407A Discus recip, 60 Hz, AC) | R407A |
| compressors | Copeland 4DCNR20ML-TSK (R407C Discus recip, 60 Hz, AC) | R407C |
| compressors | Copeland 4DCNR20ML-TSK (R407F Discus recip, 60 Hz, AC) | R407F |
| compressors | Copeland 4DCNR20ML-TSK (R448A Discus recip, 60 Hz, MD) | R448A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.