Catalog · Copeland

Copeland 4DENF47KL-TSK (R407C Discus recip, 50 Hz, LD)

Compressor — R407C compressor — 44.5 kW cooling, 18.18 kW input, COP 2.45 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 4DENF47KL-TSK (R407C Discus recip, 50 Hz, LD)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C44.46 kW
Input power @ 7.2/54.4 °C18.18 kW
COP @ 7.2/54.4 °C2.45

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 108.863.902.27
-40 / 305.674.241.34
-30 / 1015.424.893.15
-30 / 3011.296.001.88
-30 / 604.266.070.70
-20 / 1025.055.664.43
-20 / 3019.477.672.54
-20 / 6010.809.281.16

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 4DENF47KL-TSK (R407A Discus recip, 50 Hz, LD)R407A
compressorsCopeland 4DENF47KL-TSK (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 4DENF47KL-TSK (R407C Discus recip, 60 Hz, LD)R407C
compressorsCopeland 4DENF47KL-TSK (R407F Discus recip, 50 Hz, LD)R407F
compressorsCopeland 4DENF47KL-TSK (R407F Discus recip, 60 Hz, LD)R407F
compressorsCopeland 4DENF47KL-TSK (R448A Discus recip, 50 Hz, LD)R448A
compressorsCopeland 4DENF47KL-TSK (R448A Discus recip, 60 Hz, LD)R448A
compressorsCopeland 4DENF47KL-TSK (R449A Discus recip, 50 Hz, LD)R449A
compressorsCopeland 4DENF47KL-TSK (R449A Discus recip, 60 Hz, LD)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy