Compressor — R448A compressor with a 10-coefficient AHRI 540 map.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 4DJDF76KL-TSK (R448A Discus recip, 60 Hz, LD) |
| Refrigerant | R448A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 47.2 / 0.0 K |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 10 | 18.24 | 7.74 | 2.36 |
| -40 / 30 | 13.83 | 9.16 | 1.51 |
| -30 / 10 | 31.75 | 9.73 | 3.26 |
| -30 / 30 | 25.69 | 12.53 | 2.05 |
| -30 / 60 | 12.19 | 14.18 | 0.86 |
| -20 / 10 | 50.58 | 11.20 | 4.52 |
| -20 / 30 | 41.65 | 15.25 | 2.73 |
| -20 / 60 | 24.64 | 19.81 | 1.24 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.