Compressor — R454A compressor — 52.1 kW cooling, 17.65 kW input, COP 2.95 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 4YBNF40KL-TSK (R454A Discus recip, 50 Hz, LD) |
| Refrigerant | R454A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 47.2 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 52.12 kW |
| Input power @ 7.2/54.4 °C | 17.65 kW |
| COP @ 7.2/54.4 °C | 2.95 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 10 | 11.37 | 5.04 | 2.26 |
| -40 / 30 | 8.40 | 5.83 | 1.44 |
| -30 / 10 | 19.74 | 6.30 | 3.13 |
| -30 / 30 | 15.45 | 7.84 | 1.97 |
| -30 / 60 | 8.59 | 8.91 | 0.96 |
| -20 / 10 | 31.87 | 7.19 | 4.43 |
| -20 / 30 | 25.73 | 9.80 | 2.63 |
| -20 / 60 | 15.37 | 12.22 | 1.26 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 4YBNF40KL-TSK (R454A Discus recip, 60 Hz, LD) | R454A |
| compressors | Copeland 4YBNF40KL-TSK (R454C Discus recip, 50 Hz, LD) | R454C |
| compressors | Copeland 4YBNF40KL-TSK (R454C Discus recip, 60 Hz, LD) | R454C |
| compressors | Copeland 4YBNF40KL-TSK (R455A Discus recip, 50 Hz, LD) | R455A |
| compressors | Copeland 4YBNF40KL-TSK (R455A Discus recip, 60 Hz, LD) | R455A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.