Catalog · Copeland

Copeland 4YENF36KL-TSK (R454A Discus recip, 60 Hz, LD)

Compressor — R454A compressor — 57.7 kW cooling, 19.69 kW input, COP 2.93 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 4YENF36KL-TSK (R454A Discus recip, 60 Hz, LD)
RefrigerantR454A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C57.67 kW
Input power @ 7.2/54.4 °C19.69 kW
COP @ 7.2/54.4 °C2.93

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 1012.315.462.25
-40 / 309.066.311.44
-30 / 1021.416.833.14
-30 / 3016.738.481.97
-30 / 609.269.610.96
-20 / 1034.607.804.44
-20 / 3027.9310.632.63
-20 / 6016.6213.201.26

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 4YENF36KL-TSK (R454A Discus recip, 50 Hz, LD)R454A
compressorsCopeland 4YENF36KL-TSK (R454C Discus recip, 50 Hz, LD)R454C
compressorsCopeland 4YENF36KL-TSK (R454C Discus recip, 60 Hz, LD)R454C
compressorsCopeland 4YENF36KL-TSK (R455A Discus recip, 50 Hz, LD)R455A
compressorsCopeland 4YENF36KL-TSK (R455A Discus recip, 60 Hz, LD)R455A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy