Catalog · Copeland

Copeland 6DBNR32ML-TSK (R407F Discus recip, 60 Hz, AC)

Compressor — R407F compressor — 103.5 kW cooling, 33.41 kW input, COP 3.10 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6DBNR32ML-TSK (R407F Discus recip, 60 Hz, AC)
RefrigerantR407F
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C103.50 kW
Input power @ 7.2/54.4 °C33.41 kW
COP @ 7.2/54.4 °C3.10

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3077.4919.653.94
-10 / 4063.6122.402.84
-10 / 6048.5425.791.88
0 / 30119.3821.185.64
0 / 40100.5025.303.97
0 / 6084.5832.142.63
10 / 30175.2621.388.20
10 / 40142.2426.855.30
10 / 60107.2037.102.89

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6DBNR32ML-TSK (R407A Discus recip, 60 Hz, AC)R407A
compressorsCopeland 6DBNR32ML-TSK (R407C Discus recip, 60 Hz, AC)R407C
compressorsCopeland 6DBNR32ML-TSK (R407F Discus recip, 50 Hz, AC)R407F

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy