Catalog · Copeland

Copeland 6DBXR32ME-TSK (R404A Discus recip, 50 Hz, AC)

Compressor — R404A compressor — 74.9 kW cooling, 27.99 kW input, COP 2.68 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6DBXR32ME-TSK (R404A Discus recip, 50 Hz, AC)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C74.89 kW
Input power @ 7.2/54.4 °C27.99 kW
COP @ 7.2/54.4 °C2.68

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3061.2316.973.61
-10 / 4053.4019.332.76
-10 / 6034.4022.461.53
0 / 3094.5318.155.21
0 / 4082.9821.593.84
0 / 6055.8626.922.08
10 / 30135.2918.187.44
10 / 40120.2422.835.27
10 / 6085.3930.632.79

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6DBXR32ME-TSK (R407A Discus recip, 60 Hz, AC)R407A
compressorsCopeland 6DBXR32ME-TSK (R407C Discus recip, 50 Hz, MD)R407C
compressorsCopeland 6DBXR32ME-TSK (R407C Discus recip, 60 Hz, MD)R407C
compressorsCopeland 6DBXR32ME-TSK (R407F Discus recip, 50 Hz, AC)R407F
compressorsCopeland 6DBXR32ME-TSK (R407F Discus recip, 60 Hz, AC)R407F

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy