Catalog · Copeland

Copeland 6DHNF93KL-TSK (R407F Discus recip, 60 Hz, LD)

Compressor — R407F compressor — 165.2 kW cooling, 37.08 kW input, COP 4.46 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6DHNF93KL-TSK (R407F Discus recip, 60 Hz, LD)
RefrigerantR407F
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C165.24 kW
Input power @ 7.2/54.4 °C37.08 kW
COP @ 7.2/54.4 °C4.46

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 1022.6210.742.11
-40 / 3015.8711.461.38
-30 / 1033.239.383.54
-30 / 3028.6614.921.92
-30 / 6012.9517.200.75
-20 / 1052.368.056.50
-20 / 3047.1818.302.58
-20 / 6026.5423.321.14

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6DHNF93KL-TSK (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 6DHNF93KL-TSK (R407C Discus recip, 60 Hz, LD)R407C
compressorsCopeland 6DHNF93KL-TSK (R407F Discus recip, 50 Hz, LD)R407F

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy