Compressor — R407F compressor — 89.8 kW cooling, 30.61 kW input, COP 2.93 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6DHNR35ME-TSK (R407F Discus recip, 50 Hz, MD) |
| Refrigerant | R407F |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 26.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 89.82 kW |
| Input power @ 7.2/54.4 °C | 30.61 kW |
| COP @ 7.2/54.4 °C | 2.93 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 54.71 | 7.61 | 7.19 |
| -20 / 30 | 40.12 | 15.42 | 2.60 |
| -20 / 60 | 27.94 | 20.95 | 1.33 |
| -10 / 30 | 63.77 | 18.18 | 3.51 |
| -10 / 60 | 41.16 | 24.92 | 1.65 |
| 0 / 30 | 92.58 | 20.22 | 4.58 |
| 0 / 60 | 60.22 | 30.01 | 2.01 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6DHNR35ME-AWX (R134A Discus recip, 60 Hz, AC) | R134a |
| compressors | Copeland 6DHNR35ME-AWX (R404A Discus recip, 60 Hz, MD) | R404A |
| compressors | Copeland 6DHNR35ME-TSK (R407A Discus recip, 60 Hz, MD) | R407A |
| compressors | Copeland 6DHNR35ME-TSK (R407F Discus recip, 60 Hz, MD) | R407F |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.