Compressor — R404A compressor — 99.9 kW cooling, 47.85 kW input, COP 2.09 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6DJNF11ME-AWX (R404A Discus recip, 60 Hz, LD) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 45.8 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 99.89 kW |
| Input power @ 7.2/54.4 °C | 47.85 kW |
| COP @ 7.2/54.4 °C | 2.09 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 45.8 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 10 | 34.21 | 13.93 | 2.46 |
| -40 / 30 | 24.94 | 16.02 | 1.56 |
| -40 / 50 | 15.97 | 16.90 | 0.94 |
| -30 / 10 | 56.21 | 16.87 | 3.33 |
| -30 / 30 | 43.07 | 20.92 | 2.06 |
| -30 / 50 | 29.43 | 24.05 | 1.22 |
| -20 / 10 | 86.24 | 19.27 | 4.48 |
| -20 / 30 | 67.36 | 25.47 | 2.64 |
| -20 / 50 | 47.18 | 31.02 | 1.52 |
| -10 / 10 | 125.37 | 20.77 | 6.04 |
| -10 / 30 | 98.90 | 29.30 | 3.38 |
| -10 / 50 | 70.34 | 37.46 | 1.88 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6DJNF11ME-TSK (R407A Discus recip, 60 Hz, LD) | R407A |
| compressors | Copeland 6DJNF11ME-TSK (R407C Discus recip, 60 Hz, LD) | R407C |
| compressors | Copeland 6DJNF11ME-TSK (R407F Discus recip, 50 Hz, LD) | R407F |
| compressors | Copeland 6DJNF11ME-TSK (R407F Discus recip, 60 Hz, LD) | R407F |
| compressors | Copeland 6DJNF11ME-TSK (R448A Discus recip, 60 Hz, LT) | R448A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.