Catalog · Copeland

Copeland 6DJNF11ME-AWX (R404A Discus recip, 60 Hz, LD)

Compressor — R404A compressor — 99.9 kW cooling, 47.85 kW input, COP 2.09 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6DJNF11ME-AWX (R404A Discus recip, 60 Hz, LD)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool45.8 / 0.0 K
Cooling capacity @ 7.2/54.4 °C99.89 kW
Input power @ 7.2/54.4 °C47.85 kW
COP @ 7.2/54.4 °C2.09

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 45.8 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 1034.2113.932.46
-40 / 3024.9416.021.56
-40 / 5015.9716.900.94
-30 / 1056.2116.873.33
-30 / 3043.0720.922.06
-30 / 5029.4324.051.22
-20 / 1086.2419.274.48
-20 / 3067.3625.472.64
-20 / 5047.1831.021.52
-10 / 10125.3720.776.04
-10 / 3098.9029.303.38
-10 / 5070.3437.461.88

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6DJNF11ME-TSK (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 6DJNF11ME-TSK (R407C Discus recip, 60 Hz, LD)R407C
compressorsCopeland 6DJNF11ME-TSK (R407F Discus recip, 50 Hz, LD)R407F
compressorsCopeland 6DJNF11ME-TSK (R407F Discus recip, 60 Hz, LD)R407F
compressorsCopeland 6DJNF11ME-TSK (R448A Discus recip, 60 Hz, LT)R448A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy