Copeland 6DJNR40ME-AWX (R404A Discus recip, 60 Hz, MT)

Compressor — R404A compressor — 110.7 kW cooling, 47.80 kW input, COP 2.32 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6DJNR40ME-AWX (R404A Discus recip, 60 Hz, MT)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool37.5 / 0.0 K
Cooling capacity @ 7.2/54.4 °C110.71 kW
Input power @ 7.2/54.4 °C47.80 kW
COP @ 7.2/54.4 °C2.32

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 37.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 1034.3013.992.45
-40 / 3023.6215.571.52
-30 / 1055.9417.113.27
-30 / 3042.6321.052.03
-30 / 5028.1022.801.23
-20 / 1087.1419.494.47
-20 / 3068.3825.782.65
-20 / 5046.8930.461.54
0 / 30149.5032.404.61
0 / 50105.6342.882.46

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6DJNR40ME-AWX (R134A Discus recip, 60 Hz, AC)R134a
compressorsCopeland 6DJNR40ME-TSN (R407A Discus recip, 60 Hz, MT)R407A
compressorsCopeland 6DJNR40ME-TSE (R407F Discus recip, 50 Hz, MD)R407F
compressorsCopeland 6DJNR40ME-TSN (R407F Discus recip, 60 Hz, MT)R407F
compressorsCopeland 6DJNR40ME-TSE (R449A Discus recip, 60 Hz, MD)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy