Compressor — R407A compressor — 124.6 kW cooling, 40.80 kW input, COP 3.05 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6DMXR37ML-TSN (R407A Discus recip, 60 Hz, AC) |
| Refrigerant | R407A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 124.57 kW |
| Input power @ 7.2/54.4 °C | 40.80 kW |
| COP @ 7.2/54.4 °C | 3.05 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 88.63 | 24.41 | 3.63 |
| -10 / 40 | 79.24 | 27.43 | 2.89 |
| -10 / 60 | 54.08 | 32.62 | 1.66 |
| 0 / 30 | 133.25 | 26.01 | 5.12 |
| 0 / 40 | 117.63 | 31.02 | 3.79 |
| 0 / 60 | 79.56 | 39.02 | 2.04 |
| 10 / 30 | 202.38 | 26.40 | 7.67 |
| 10 / 40 | 180.23 | 33.92 | 5.31 |
| 10 / 60 | 128.63 | 45.74 | 2.81 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6DMXR37ML-TSN (R407C Discus recip, 60 Hz, AC) | R407C |
| compressors | Copeland 6DMXR37ML-TSN (R407F Discus recip, 50 Hz, AC) | R407F |
| compressors | Copeland 6DMXR37ML-TSN (R407F Discus recip, 60 Hz, AC) | R407F |
| compressors | Copeland 6DMXR37ML-TSN (R448A Discus recip, 60 Hz, MD) | R448A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.