Compressor — R407F compressor — 124.9 kW cooling, 45.14 kW input, COP 2.77 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6DSNR40ML-TSE (R407F Discus recip, 60 Hz, MD) |
| Refrigerant | R407F |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 26.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 124.95 kW |
| Input power @ 7.2/54.4 °C | 45.14 kW |
| COP @ 7.2/54.4 °C | 2.77 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 72.59 | 15.75 | 4.61 |
| -20 / 30 | 56.27 | 20.67 | 2.72 |
| -20 / 60 | 34.69 | 27.18 | 1.28 |
| -10 / 30 | 89.03 | 24.73 | 3.60 |
| -10 / 60 | 58.69 | 34.86 | 1.68 |
| 0 / 30 | 135.32 | 28.34 | 4.78 |
| 0 / 60 | 88.81 | 42.92 | 2.07 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6DSNR40ML-TSN (R407F Discus recip, 50 Hz, MD) | R407F |
| compressors | Copeland 6DSNR40ML-TSE (R448A Discus recip, 60 Hz, MD) | R448A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.