Compressor — R407A compressor — 103.5 kW cooling, 33.41 kW input, COP 3.10 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6DYNR32ML-TSK (R407A Discus recip, 60 Hz, AC) |
| Refrigerant | R407A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 103.50 kW |
| Input power @ 7.2/54.4 °C | 33.41 kW |
| COP @ 7.2/54.4 °C | 3.10 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 77.49 | 19.65 | 3.94 |
| -10 / 40 | 63.61 | 22.40 | 2.84 |
| -10 / 60 | 48.54 | 25.79 | 1.88 |
| 0 / 30 | 119.38 | 21.18 | 5.64 |
| 0 / 40 | 100.50 | 25.30 | 3.97 |
| 0 / 60 | 84.58 | 32.14 | 2.63 |
| 10 / 30 | 175.26 | 21.38 | 8.20 |
| 10 / 40 | 142.24 | 26.85 | 5.30 |
| 10 / 60 | 107.20 | 37.10 | 2.89 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6DYNR32ML-TSK (R407C Discus recip, 60 Hz, AC) | R407C |
| compressors | Copeland 6DYNR32ML-TSK (R407F Discus recip, 50 Hz, AC) | R407F |
| compressors | Copeland 6DYNR32ML-TSK (R407F Discus recip, 60 Hz, AC) | R407F |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.