Compressor — R407F compressor — 114.2 kW cooling, 40.67 kW input, COP 2.81 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6YGNR35ME-TSN (R407F Discus recip, 60 Hz, MD) |
| Refrigerant | R407F |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 26.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 114.23 kW |
| Input power @ 7.2/54.4 °C | 40.67 kW |
| COP @ 7.2/54.4 °C | 2.81 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 52.95 | 12.11 | 4.37 |
| -20 / 30 | 54.57 | 20.70 | 2.64 |
| -20 / 60 | 27.79 | 23.74 | 1.17 |
| -10 / 30 | 81.81 | 24.10 | 3.39 |
| -10 / 60 | 53.03 | 32.57 | 1.63 |
| 0 / 30 | 122.32 | 25.70 | 4.76 |
| 0 / 60 | 78.00 | 39.52 | 1.97 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6YGNR35ME-TSN (R407A Discus recip, 60 Hz, MD) | R407A |
| compressors | Copeland 6YGNR35ME-TSN (R407C Discus recip, 60 Hz, AC) | R407C |
| compressors | Copeland 6YGNR35ME-FSD (R454A Discus recip, 60 Hz, MD) | R454A |
| compressors | Copeland 6YGNR35ME-FSD (R454C Discus recip, 60 Hz, MD) | R454C |
| compressors | Copeland 6YGNR35ME-FSD (R455A Discus recip, 60 Hz, MD) | R455A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.