Catalog · Copeland

Copeland 6YRNR39ME-TSE (R449A Discus recip, 60 Hz, MD)

Compressor — R449A compressor — 126.3 kW cooling, 44.87 kW input, COP 2.81 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6YRNR39ME-TSE (R449A Discus recip, 60 Hz, MD)
RefrigerantR449A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K
Cooling capacity @ 7.2/54.4 °C126.30 kW
Input power @ 7.2/54.4 °C44.87 kW
COP @ 7.2/54.4 °C2.81

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1071.2715.614.57
-20 / 3057.7621.022.75
-20 / 6036.2628.131.29
-10 / 3090.6924.803.66
-10 / 6061.0435.771.71
0 / 30136.2627.934.88
0 / 6091.0843.512.09

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6YRNR39ME-TSN (R407A Discus recip, 60 Hz, AC)R407A
compressorsCopeland 6YRNR39ME-TSN (R407C Discus recip, 60 Hz, AC)R407C
compressorsCopeland 6YRNR39ME-TSN (R407F Discus recip, 60 Hz, AC)R407F
compressorsCopeland 6YRNR39ME-TSE (R448A Discus recip, 60 Hz, MD)R448A
compressorsCopeland 6YRNR39ME-TSN (R454A Discus recip, 60 Hz, MD)R454A
compressorsCopeland 6YRNR39ME-TSN (R454C Discus recip, 60 Hz, MD)R454C
compressorsCopeland 6YRNR39ME-TSN (R455A Discus recip, 60 Hz, MD)R455A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy