Compressor — R407C compressor — 125.4 kW cooling, 42.86 kW input, COP 2.93 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6YSNR39ME-TSN (R407C Discus recip, 60 Hz, AC) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 125.40 kW |
| Input power @ 7.2/54.4 °C | 42.86 kW |
| COP @ 7.2/54.4 °C | 2.93 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 89.20 | 24.77 | 3.60 |
| -10 / 40 | 77.47 | 27.77 | 2.79 |
| -10 / 60 | 49.82 | 34.01 | 1.46 |
| 0 / 30 | 146.10 | 27.83 | 5.25 |
| 0 / 40 | 131.35 | 32.19 | 4.08 |
| 0 / 60 | 84.55 | 42.37 | 2.00 |
| 10 / 30 | 204.25 | 30.03 | 6.80 |
| 10 / 40 | 189.89 | 35.20 | 5.39 |
| 10 / 60 | 130.69 | 48.19 | 2.71 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6YSNR39ME-TSN (R407A Discus recip, 60 Hz, AC) | R407A |
| compressors | Copeland 6YSNR39ME-TSN (R407F Discus recip, 60 Hz, AC) | R407F |
| compressors | Copeland 6YSNR39ME-TSE (R448A Discus recip, 60 Hz, MD) | R448A |
| compressors | Copeland 6YSNR39ME-TSE (R449A Discus recip, 60 Hz, MD) | R449A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.