Compressor — R454C compressor with a 10-coefficient AHRI 540 map.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 6YUXR48ME-AWD (R454C Discus recip, 60 Hz, MD) |
| Refrigerant | R454C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 0.0 K |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 81.59 | 18.19 | 4.49 |
| -20 / 30 | 65.61 | 24.63 | 2.66 |
| -20 / 60 | 39.73 | 30.57 | 1.30 |
| -10 / 10 | 122.56 | 17.48 | 7.01 |
| -10 / 30 | 102.08 | 28.54 | 3.58 |
| -10 / 60 | 62.27 | 39.35 | 1.58 |
| 0 / 30 | 150.70 | 30.00 | 5.02 |
| 0 / 60 | 94.57 | 47.75 | 1.98 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 6YUXR48ME-AWD (R454A Discus recip, 60 Hz, MD) | R454A |
| compressors | Copeland 6YUXR48ME-AWD (R455A Discus recip, 60 Hz, MD) | R455A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.