Catalog · Copeland

Copeland 6YZNF10ME-TSE (R407F Discus recip, 60 Hz, LD)

Compressor — R407F compressor — 104.4 kW cooling, 53.31 kW input, COP 1.96 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6YZNF10ME-TSE (R407F Discus recip, 60 Hz, LD)
RefrigerantR407F
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C104.42 kW
Input power @ 7.2/54.4 °C53.31 kW
COP @ 7.2/54.4 °C1.96

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 1030.0912.322.44
-40 / 3022.3714.561.54
-30 / 1052.3816.183.24
-30 / 3040.4520.291.99
-30 / 6019.9123.360.85
-20 / 1086.0019.674.37
-20 / 3066.1925.972.55
-20 / 6041.6033.261.25

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6YZNF10ME-TSE (R404A Discus recip, 60 Hz, LD)R404A
compressorsCopeland 6YZNF10ME-TSE (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 6YZNF10ME-TSE (R407C Discus recip, 60 Hz, LD)R407C
compressorsCopeland 6YZNF10ME-TSE (R448A Discus recip, 60 Hz, LD)R448A
compressorsCopeland 6YZNF10ME-TSE (R449A Discus recip, 60 Hz, LD)R449A
compressorsCopeland 6YZNF10ME-AWD (R507 Discus recip, 60 Hz, LT)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy