Copeland 6YZNR48ME-TSE (R448A Discus recip, 60 Hz, MD)

Compressor — R448A compressor with a 10-coefficient AHRI 540 map.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6YZNR48ME-TSE (R448A Discus recip, 60 Hz, MD)
RefrigerantR448A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1085.5819.394.41
-20 / 3069.6925.962.68
-20 / 6042.0433.831.24
-10 / 30109.0530.593.56
-10 / 6073.0943.401.68
0 / 30163.3234.334.76
0 / 60109.3952.832.07

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6YZNR48ME-TSE (R22 Discus recip, 60 Hz, MD)R22
compressorsCopeland 6YZNR48ME-TSE (R404A Discus recip, 60 Hz, MD)R404A
compressorsCopeland 6YZNR48ME-TSE (R407A Discus recip, 60 Hz, MD)R407A
compressorsCopeland 6YZNR48ME-TSE (R407C Discus recip, 60 Hz, MD)R407C
compressorsCopeland 6YZNR48ME-TSE (R407F Discus recip, 60 Hz, MD)R407F
compressorsCopeland 6YZNR48ME-TSE (R449A Discus recip, 60 Hz, MD)R449A
compressorsCopeland 6YZNR48ME-TSE (R507 Discus recip, 60 Hz, MD)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy