Catalog · Copeland

Copeland AFE14C5E-IAZ (R449A hermetic recip, 50 Hz, LT)

Compressor — R449A compressor — 1.0 kW cooling, 0.67 kW input, COP 1.47 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland AFE14C5E-IAZ (R449A hermetic recip, 50 Hz, LT)
RefrigerantR449A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool38.9 / 0.0 K
Cooling capacity @ 7.2/54.4 °C0.98 kW
Input power @ 7.2/54.4 °C0.67 kW
COP @ 7.2/54.4 °C1.47

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 38.9 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 300.310.221.41
-30 / 400.270.231.16
-20 / 300.500.281.81
-20 / 400.430.301.45
-20 / 600.290.340.84
-10 / 300.800.342.36
-10 / 400.680.381.79
-10 / 600.470.451.03

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland AFE14C5E-IAZ (R448A hermetic recip, 50 Hz, LT)R448A
compressorsCopeland AFE14C5E-IAA (R448A hermetic recip, 60 Hz, LT)R448A
compressorsCopeland AFE14C5E-IAA (R449A hermetic recip, 60 Hz, LT)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy