Copeland AFE26C5E-CAA (R404A hermetic recip, 60 Hz, EA)

Compressor — R404A compressor — 2.0 kW cooling, 1.61 kW input, COP 1.21 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland AFE26C5E-CAA (R404A hermetic recip, 60 Hz, EA)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool40.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C1.95 kW
Input power @ 7.2/54.4 °C1.61 kW
COP @ 7.2/54.4 °C1.21

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 40.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -34 to -9 °C, condensing 21 to 60 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 300.790.571.37
-30 / 400.660.611.08
-30 / 600.390.640.62
-20 / 301.260.741.71
-20 / 401.060.791.35
-20 / 600.650.860.75
-10 / 301.900.942.02
-10 / 401.611.011.60
-10 / 601.001.130.89

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland AFE26C5E-CAA (R448A hermetic recip, 60 Hz, LT)R448A
compressorsCopeland AFE26C5E-CAA (R449A hermetic recip, 60 Hz, LT)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy