Catalog · Copeland

Copeland ASE14C4E-IAA (R404A hermetic recip, 60 Hz, MT)

Compressor — R404A compressor — 0.6 kW cooling, 0.49 kW input, COP 1.31 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ASE14C4E-IAA (R404A hermetic recip, 60 Hz, MT)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.5 / 0.0 K
Cooling capacity @ 7.2/54.4 °C0.64 kW
Input power @ 7.2/54.4 °C0.49 kW
COP @ 7.2/54.4 °C1.31

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 400.340.291.15
-10 / 400.510.341.49
-10 / 500.410.371.11
-10 / 600.310.390.79
0 / 400.750.401.90
0 / 500.600.431.39
0 / 600.460.470.98

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ASE14C4E-IAA (R448A hermetic recip, 60 Hz, MT)R448A
compressorsCopeland ASE14C4E-IAA (R449A hermetic recip, 60 Hz, MT)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy