Catalog · Copeland

Copeland ASE39C5E-CAZ (R449A hermetic recip, 50 Hz, MT)

Compressor — R449A compressor — 1.3 kW cooling, 0.83 kW input, COP 1.62 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ASE39C5E-CAZ (R449A hermetic recip, 50 Hz, MT)
RefrigerantR449A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.5 / 0.0 K
Cooling capacity @ 7.2/54.4 °C1.35 kW
Input power @ 7.2/54.4 °C0.83 kW
COP @ 7.2/54.4 °C1.62

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 400.640.401.58
-10 / 400.990.502.00
-10 / 500.810.531.52
-10 / 600.660.561.18
0 / 401.470.612.41
0 / 501.260.671.89
0 / 601.080.711.52

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ASE39C5E-CAZ (R448A hermetic recip, 50 Hz, MT)R448A
compressorsCopeland ASE39C5E-CAA (R448A hermetic recip, 60 Hz, MT)R448A
compressorsCopeland ASE39C5E-CAA (R449A hermetic recip, 60 Hz, MT)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy