Compressor — R407C compressor — 6.2 kW cooling, 2.27 kW input, COP 2.71 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland CR30K6ME-PF1 (R407C hermetic recip, 50 Hz, HT) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 19.4 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 6.17 kW |
| Input power @ 7.2/54.4 °C | 2.27 kW |
| COP @ 7.2/54.4 °C | 2.71 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 19.4 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 40 | 3.30 | 1.49 | 2.21 |
| -10 / 50 | 2.63 | 1.54 | 1.71 |
| 0 / 40 | 6.02 | 1.78 | 3.38 |
| 0 / 50 | 5.05 | 1.97 | 2.56 |
| 0 / 60 | 3.84 | 2.11 | 1.82 |
| 10 / 40 | 10.55 | 1.89 | 5.59 |
| 10 / 50 | 8.84 | 2.22 | 3.99 |
| 10 / 60 | 6.99 | 2.48 | 2.82 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |