Catalog · Copeland

Copeland CR37K6ME-TFD (R407C hermetic recip, 50 Hz, HT)

Compressor — R407C compressor — 8.1 kW cooling, 2.89 kW input, COP 2.81 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland CR37K6ME-TFD (R407C hermetic recip, 50 Hz, HT)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool19.4 / 8.3 K
Cooling capacity @ 7.2/54.4 °C8.12 kW
Input power @ 7.2/54.4 °C2.89 kW
COP @ 7.2/54.4 °C2.81

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 19.4 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 404.891.942.53
-10 / 503.741.901.97
0 / 408.362.343.57
0 / 506.922.462.81
0 / 605.312.492.13
10 / 4013.232.694.93
10 / 5011.312.963.82
10 / 609.153.162.90

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland CR37K6ME-TFD (R407C hermetic recip, 60 Hz, HT)R407C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy