Compressor — R407C compressor — 8.7 kW cooling, 3.06 kW input, COP 2.85 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland CR41K6ME-TFM (R407C hermetic recip, 50 Hz, HT) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 19.4 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 8.72 kW |
| Input power @ 7.2/54.4 °C | 3.06 kW |
| COP @ 7.2/54.4 °C | 2.85 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 19.4 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 40 | 5.14 | 2.05 | 2.51 |
| -10 / 50 | 3.95 | 2.16 | 1.83 |
| 0 / 40 | 9.05 | 2.37 | 3.82 |
| 0 / 50 | 7.37 | 2.66 | 2.77 |
| 0 / 60 | 5.72 | 2.89 | 1.98 |
| 10 / 40 | 14.47 | 2.49 | 5.80 |
| 10 / 50 | 12.21 | 2.96 | 4.12 |
| 10 / 60 | 9.84 | 3.36 | 2.93 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.